Speciality cables

3 CORE FLAT CABLES

For troublefree working these connecting cables are just as important as winding wires are for the submersible pump motors.
" SHREE NAKODA " 3 Core Flat Cables are manufactured keeping in mind the severely difficult conditions in which these are required to operate. The individual flexible conductors are made from electrolytic grade bright copper. The wires are drawn, annealed and bunched properly to ensure long life. Each of these three flexible copper conductors is insulated with a specially formulated PVC compound and the cores are laid-up in Flat Parallel Position. The outer sheath of the cable is made from a special grade of abrasion resistant PVC compound impervious to water, grease, oil etc.
 
 

CONDUCTOR Nominal Area sq. mm 1.5 2.5 4.0 6.0 10.0 16.0 25.0 35.0 50.0 70.0 95.0
Nos. & Size (mm) of Wires 22/.3 36/.3 57/.3 85/.3 140/.3 226/.3 354/.3 495/.3   440/.45 485/.5
INSULATOR Radial thickness mm (nominal) 0.8 0.9 1.0  1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6
Core Diameter mm (nominal 3.25 3.85 4.65 5.30 6.60 8.20 10.10 11.50 13.6 15.30 18.10
SHEET Thickness of sheath mm (nominal) 1.15 1.15 1.15 1.15 1.4 1.4 2.0 2.0 2.2 2.2 2.4
Overall dimensions    w mm

t mm

12.8
6.0
14.6
6.4
17.2
7.4
18.7
7.9
23.7
9.9
28.0
11.4
35.5
14.7
39.5
16.2
45.5
18.3
51.0
20.0
60.0
23.5
MECHANICAL
FIELD
Conductor - elongation at break

13.5% min.

Insulation - tensile strength

12.5 n/mm2 (min)

Insulation - elongation at break

150% min.

sheath - tensile strength

12.5 n/mm2 (min)

sheath - elongation at break

150% min.

ELECTRICAL Maximum Resistance
Per km at 20o c ohms
 
11.87 7.254 4.583 3.073 1.866 1.178 0.7523 0.528 0.367 0.2587 0.196
Current carrying capacity at an ambient temp. of 40o c Amps 14 18 26 31 42 57 72 90 115 143 165
Max Conductor Temp

70o c

Effect of Humidity

Nil

COLOUR Core

RED YELLOW BLUE

Sheath

BLACK

WT Approximate weight kg/km 126.0 176.0 255.0 318.0 526.0 786.0 1267.0 1644.0 2082.0 2833.0 3622.0


DOUBLE SHEATHED YELLOW CABLES FOR DEWATERING PUMPS
 

Size
(No. of cores x Core Area)
sq.mm

Nominal Core Dia mm

Inner Sheath Nominal O.D

Outer Sheath Nominal O.D

4 x 2.5

4.05

12.10

15.05

4 x 4

4.61

13.50

16.00

4 x 6

5.30

14.70

17.00

4 x

     

Cables for sewage and slurry pumps should be able to withstand abrasion, prevent ingress of water along the inside of the cables and be resistant to acidic fluids and other chemicals. Bright yellow coloured double jacketed "SHREE NAKODA" cables are successfully running dewatering pumps. The range and size is as per the table.

 